Skip to main content

P27000 Universal Isolated Signal Conditioner | Calibrated switching of 480 input and output ranges | Isolation up to 1000 V

Description

P27000 Universal Isolated Signal Conditioner | Calibrated switching of 480 input and output ranges | Isolation up to 1000 V

The "Multimeter" among the signal conditioners. With 480 switchable calibrated ranges and broad-range power supply.

  • Flexible and extremely precise
    Calibrated range selection without complicated readjustments
  • Broad-range power supply
    20 … 253 V AC/DC
  • Compact design
    12.5 mm modular housing; up to 80 active isolators per meter of mounting rail
  • Quick and easy configuration
    Housing can be easily opened
  • Pluggable screw terminals
    Simple, time-saving assembly and prewiring of enclosures
  • 3-port separation
    Protection against incorrect measurements or damage
  • Maximum accuracy
  • Specific test report
    Following EN 10204 2.2
  • Protective separation
    According to EN 61140. Protection against unacceptably high voltages (for example, with shunt measurements at high potentials or in 3-phase systems)
  • Maximum reliability 
    No repair and failure costs
  • 5-year warranty

The isolation amplifiers provide safe galvanic isolation for any input signals from ±20 mV to ±200 V and from ±0.1 mA to ±100 mA.

We look forward to hearing from you!
Contact Us

Technical details

Function: Current and voltage measurement
Input: 0 ... (±)0.1 mA up to 0 ... (±)100 mA, 0 ... (±)10 V, 0 ... (±)20 mA, 0 ... (±)20 mV up to 0 ... (±)200 V, 4 ... 20 mA
Output: 0 ... (±)10 V, 0 ... (±)20 mA, 4 ... 20 mA
Isolation AC/DC: up to 1,000 V
Test Voltage: 5 kV AC
Power Supply: 22 ... 230 V AC/DC
Cutoff Frequency: Switchable cutoff frequency 10 kHz or 10 Hz, other cutoff frequency on request
Ambient operating temperature: –10 ... 70 °C
Dimensions (W x L x H): 12.5 x 99 x 111 mm
Special features: Calibrated switching of 480 input and output ranges using DIP switches, The "Multimeter" among the signal conditioners
Product Category: Isolated Signal Conditioner

Downloads

Manuals

[1302] User Manual (DE, EN, FR)
P27000
Version 06
[10953] User Manual (DE, EN)
P27000-S008
Version 04
[10880] User Manual (DE, EN)
P27000-S009
Version 04
[10940] User Manual (DE, EN)
P27000-S0011
Version 01

Data Sheets

[1291] Data sheet
P27000
Product Description | Specifications | Product Range

Certificates

[12124] EU Declaration of Conformity (DE, EN, FR)
P27***H1…, P27***F1…
No. EU240613A | 2024-06-13
[14100] Quality Report (MTBF)
Document No. TX180228A
Failure Rate
[11577] Type Approval Certificate (DNV)
P270X Y1
No: TAA000011Y
Revision No: 3
[11827] Certificate of Compliance (UL)
Series P27000 through P27099...
Process Control Equipment for Use in Hazardous Locations
No. E308146 | 2018-10-29
[11771] Certificate of Compliance (UL)
Series P 27000 through P 27099...
Process Control Equipment for Use in Zone Classified Hazardous Locations
No. E3402288 | 2018-10-15
[11779] Certificate of Compliance (UL)
Series P 270**BL570
Process Control Equipment, Electrical
No. E340287 | 2019-11-22

Software

[12153] Software
VariSoft SW 108 Configuration Software
[11875] Knick Produktmakros
ePLAN P4 (.pdf)
[12144] Software
ePLAN P4 Produktmakros
[11876] Knick Produktmakros (.pdf)
ePLAN Electric P8
[12154] Software (.zip)
ePLAN P8 Produktmakros

Our service

Used in Process or Applications

In order to guarantee the optimal output, modern wind turbines contain a range of sensors whose measuring signals must be acquired, converted, and queried – in many cases over long distances.

Related Products

Relevant Blog Posts

Robust WA111 Retractable Fitting Made of Plastic for Highly Corrosive Operating Conditions

The plastic WA111 retractable fitting is a robust and cost-effective solution for corrosive processes and environments. It is equipped with a secure lock function and multiple nozzles for thorough sensor cleaning.

Successful joint project : Knick developed the special Ceramat WA 155 retractable fitting for optical probes from SOPAT

In cooperation with SOPAT, Knick developed a special Ceramat fitting for optical probes for automatic cleaning in fouling processes.

High-quality immersion fitting for mobile applications

ARD 170 enables measurements even in deep water

Modular immersion fitting as an electrically conductive variant

Knick is expanding its portfolio of fittings for liquid analysis with additional electrically conductive (EL) variants.

How to get the sensor into the process

Sensors as the direct interface to the process must be exactly matched to the chemistry of the measured medium and to the prevailing pressure and temperature conditions.