Product added to compare
Product Compare added Product Compare

P41000 TRMS AC/DC High Voltage Transducer | Input up to ±100 V | True RMS measurement

Description

P41000 TRMS AC/DC High Voltage Transducer | Input up to ±100 V | True RMS measurement

AC/DC high voltage transducer for True RMS measurement. Input signals from VIN = 60 mV AC up to VIN = 10 V AC

  • Universal usability:
    • AC Input 60 mV~ to 10 V~
    • DC output 0 (4) … 20 mA, 0 … 10 V
  • New TransShield technology
    allows for extremely compact modular housing
  • Working voltages up to 3600 V AC/DC
  • Protection against electric shock
    through protective separation up to 1800 V AC/DC according to EN 61140
  • Test voltages up to 15 kV AC
  • Excellent transmission properties:
    • Gain error Crest factor ≤ 3 < 0.5 %
    • Gain error Crest factor 3 … 5 < 1 %
    • Response time T90  < 150 ms
  • Virtually no influence from common-mode voltages:
    CMRR approx. 150 dB
  • Tremendous flexibility provided by
    • Calibrated switching of up to 16 input/output ranges
    • Up to 16 customer-specific measuring ranges
    • VariPower 20 V to 253 V AC/DC broad-range power supply
  • Reliable function even with unstable supply
  • No damage
    in the case of erroneous power connection
  • Switchable models
    minimize required device variants and save stockkeeping costs
  • Robust
    thanks to vacuum encapsulation
  • Mechanically stable
    for operation on ships, rail vehicles and land vehicles
  • 5-year warranty

The P41000 TRMS isolation amplifiers have been specially conceived for measurements of bipolar voltages ranging from millivolts to volts. They reliably isolate high potentials at the input circuit. Thanks to the true rms conversion in the transducer, even distorted input signals are captured correctly and output as so-called true rms values.

The isolating distances are designed to withstand permanent voltages up to 3600 V AC/DC and fast transients up to 20 kV.

We look forward to hearing from you!
Contact Us

Technical details

Product Category: High Voltage Transducer
Device Type: AC/DC Transducers, High Voltage Transducers, Universal Isolated Signal Conditioners
Input: (±)10 V, (±)500 mV ... (±)200 V, ≤ (±)500 mV
Output: 0 … 10 V, 0 … 20 mA, 4 … 20 mA, Others, ±20 mA
Working Voltage, Min.: 50 V, 300 V, 1000 V, 2000 V, 3600 V
Fault Class: < 0.5 %
Housing: 17.5 … 67.5 mm Modular housing
Power Supply: 24 V AC, 24 V DC, 110 / 115 V AC, 220 / 230 V AC, Broad-range power supply, Others

Downloads

Manuals

User Manual
P41000 TRMS
Version 06
P41000_TA-253.106-KNEN06_100436_s-2517432

Data Sheets

Data sheet
P41000 TRMS
Product Description | Specifications | Product Range

Certificates

[11463] EU Declaration of Conformity (DE, EN, FR)
Series VariTrans P4x000 (D*-nnnn/D*AG-nnnn/D*TRMS-nnnn)
No. EU221209A | 2023-11-29
[14140] Quality Report (MTBF)
Document No. TX180416A
Failure Rate of Series P40000

Our service

Lorem lorem ipsum ipsum dolor sit amet, consetetur sadipscing elitr, sed diam nonumy eirmod tempor invidunt ut labore et dolore magna aliquyam erat, sed diam voluptua. At vero eos et accusam et justo duo dolores et ea rebum. Stet clita kasd gubergren, no sea takimata sanctus est Lorem ipsum dolor sit amet. Lorem ipsum dolor sit amet, consetetur sadipscing elitr, sed diam nonumy eirmod tempor invidunt ut labore et dolore magna aliquyam erat, sed diam voluptua. At vero eos et accusam et justo duo dolores et ea rebum. Stet clita kasd gubergren, no sea takimata sanctus est Lorem ipsum dolor sit amet.

Used in Process or Applications

High voltage transducers and signal conditioners for the acquisition and conversion of current, voltage, temperature, speed, strain and resistance signals.

Related Products

Relevant Blog Posts

True RMS Measurement with P41000TRMS

Traditional millivolt AC transducers are very susceptible to errors due to their poor insulation and are only designed for pure sinewave measurement.