Shunt Resistors | Handles High Overloads | Immune to External Fields

Description

Shunt Resistors | Handles High Overloads | Immune to External Fields

Precise and long-term stable measurement of direct current

  • For currents up to 20 kA
    with a standard program from 10 A to 8 kA

  • Low heat loss and low space requirement
    due to small measuring voltages from 30 mV

  • Precise measurement
    with accuracy classes 0.2 and 0.5

  • Special versions for energy measuring systems on rail vehicles
    according to EN 50463

  • High overload capacity
    without residual measurement failure

  • No influence from current peaks or neighboring cables
    due to the measuring principle

  • Low temperature coefficient
    and thus small measurement failure due to temperature influences

  • Safe electrical isolation and short response times
    through a combination with measuring transducers from Knick

  • Galvanic isolation between power section and control
    up to 3.6 kV working voltage / 15 kV test voltage

  • Conversion to standard signals
    ±20 mA, ±10 V, 4 to 20 mA

  • 5 year guarantee

The meticulously produced shunt resistors feature resistor rods made of manganin with low self heating and an exceptionally low temperature coefficient. The variants with a rated voltage drop of 30 mV distinguish themselves from the 50 mV or 60 mV versions thanks to more compact dimensions and significantly lower power dissipation, which greatly reduces the effort required for electrical enclosure cooling. Knick’s transducers and signal conditioners from the P41000, P51000, P29000, P27000, and BL591 series, which are adapted optimally to the shunt resistors, are available for current measurement.

The shunt resistors and associated shunt isolators achieve very good long-term stability, which guarantees the specified accuracy over the normal periods of application of many years. Current peaks do not cause any offset or drift. Protection equipment based on current measurement benefits from the reliability and long-term stability of the measurement and achieves a particularly high level of safety performance.

We look forward to hearing from you!
Contact Us

Technical details

Function: Shunt resistor for current measurement
Input: 0 ... 1 A up to 0 ... 20 kA
Output: 0 ... 30 mV, 0 ... 50 mV, 0 ... 60 mV
Ambient operating temperature: –10 ... 55 °C
Dimensions (W x L x H): depending on the input value
Product Category: High Voltage Transducer, Isolated Signal Conditioner

Downloads

Data Sheets

[903] Data Sheet
Shunt Resistor for Direct Current Measurements from 1 A to 20 kA
Product Description | Specifications | Product Range
Version 02

Certificates

[13916] EU Declaration of Conformity (DE, EN, FR)
No. EU170803A | 2017-08-03
Maconic M...S, M...HS

Installation guides

[14541] Installation Guide (DE, EN)
Sealing Maconic Shunt Resistors / Plombensicherung von Maconic Shunt-Widerständen
Version 01

Our service

Used in Process or Applications

High voltage transducers and signal conditioners for the acquisition and conversion of current, voltage, temperature, speed, strain and resistance signals.

Related Products

Relevant Blog Posts

Knick Products Comply With UL - What Does That Mean?

There are different assessments and approaches to reach an adequate level of safety. Manufacturers are typically on the “safe” side, if they comply with recognized standards.