Passer au contenu principal

P32200 Sensor Transmitter | Input strain gauges and load cells | For safety circuits up to SIL3 | Configuration interface for PC

Description

P32200 Sensor Transmitter | Input strain gauges and load cells | For safety circuits up to SIL3 | Configuration interface for PC

The universal P32200 strain gauge transmitters provide connection possibilities for all standard strain gauge force transducers and strain gauge load cells in full bridge configuration. They can be flexibly adapted to the respective measuring task using DIP and rotary encoder switches or via an IrDA port.

  • Universal usability
    for strain gauges, pressure and load cells, and other resistive measuring bridges
  • Convenient setting of all parameters
    via IrDA interface. Uncomplicated, menu-guided adjustment also “on site“ including archiving of the configuration data.
  • Intuitive configuration
    of the basic parameters. Easy, without tools, using 4 rotary and 8 DIP switches
  • Calibrated range selection
    No complicated trimming
  • Convenient adjustment
    Zero point and sensitivity adjustable via IrDA port
  • Simulation
    of any desired output values for correct installation/commissioning
  • Protective separation
    according to EN 61140 - protection of the maintenance staff and subsequent devices against excessively high voltages up to 300 V AC/DC
  • Functional safety
    up to SIL 2 (up to SIL 3 in case of redundant configuration) with TÜV certificate Systematically developed according to EN 61508
  • High accuracy
    due to innovative circuit design
  • Minimum space consumption
    in the enclosure. Modular housing: just 6 mm wide. More transmitters per meter of DIN rail
  • Low-cost assembly
    Quick mounting, convenient connection of power supply through DIN rail bus connectors (in case of 24 V DC power supply)
  • 5-year warranty

3-port isolation with protective separation up to 300 V AC/DC according to EN 61140 ensures optimal protection of personnel and equipment as well as unaltered transmission of the measurement signals. The P32200 offer maximum performance in the smallest of spaces.

Adjusting the zero point and sensitivity to the individual strain gauge sensor is particularly convenient via the infrared port, for example using a PDA. Sensors with known characteristics can be very easily calibrated using 4 rotary encoder switches and 8 DIP switches. Special measuring tasks can be solved with SensoTrans devices that Knick configures according to individual specifications. Fixed-range devices without switches are used, for example, when manipulations or mix-ups must be precluded.

Knick offers the P32200 transmitter with SIL approval for applications with high demands on functional safety. The requirements of EN 61508 were implemented through specially developed hardware and software. The implemented fail-safe concept makes use of structural measures at the device level (redundancy of system components) and diagnostic methods for selective fault detection. The product is SIL 2 approved (EN 61508) by an authorized body (TÜV Rheinland). SIL 3 in redundant implementations

Nous attendons avec impatience votre réponse!
Nous Contacter

Détails techniques

Catégorie de produits: Convertisseur de mesure

Téléchargements

Manuals

[13390] User Manual (DE, EN, FR, ES)
ZU 0677 (Power terminal block)
Version 03
[1466] User Manual (DE, EN, FR, BR)
SensoTrans P 32200 P0/
Version 05

Fiches techniques

[1458] Fiche technique
P32200
Description du produit | Caractéristiques techniques | Gamme de produits

Certificats

[11665] TÜV Rheinland Certificate
No. 968/EZ 272.00/07 | 2007-10-12
Transmitter Series P32*** P0/1
EN 61508 |SlL2, SIL3
[11418] Certificate of Compliance (UL)
No. 20181015-E220033 | 2018-OCTOBER-15
POWER CIRCUIT AND MOTOR-MOUNTED APPARATUS
P32*00P0/**, A202*0P0..., BL520
[11256] CB Test Certificate
No. DE 2-036775 | 2022-10-11
P32000, P32100, P32200, P32300, A20210, A20220, A20230

Safety guides

[1383] Guide de sécurité SIL
P32*00P0/1
Version 02

Software

[11876] Knick Produktmakros (.pdf)
ePLAN Electric P8
[12154] Software (.zip)
ePLAN P8 Produktmakros

Notre service

Utilisé dans les processus ou les applications

Knick propose des transmetteurs industriels innovants, des sondes de haute qualité, des supports innovants, ainsi que des systèmes de nettoyage et de calibrage uniques en leur genre.

Produits apparentés

Articles de blog pertinents

Mesure de la dégradation photovoltaïque

L’ampleur de la dégradation photovoltaïque (PV) est un élément important à prendre en compte pour la conception et l’installation de systèmes. Des facteurs tels que la météo et l’exposition aux UV contribuent au déclin de la performance.