Skip to main content

A26000 Universal Isolated Signal Conditioner | Input 0…±20 mA or 0…±10 V | Current and voltage measurement

Description

A26000 Universal Isolated Signal Conditioner | Input 0…±20 mA or 0…±10 V | Current and voltage measurement

The specialist for ±10 V and ±20 mA. With calibrated range selection and broad-range power supply.

  • Flexible and extremely precise
    Calibrated range selection without complicated readjustments
  • Broad-range power supply
    VariPower 20 … 253 V AC/DC
  • Compact design
    12.5 mm modular housing; up to 80 active isolators per meter of mounting rail
  • Quick and easy configuration
    Housing can be easily opened
  • Pluggable screw terminals
    Simple, time-saving assembly and prewiring of enclosures
  • 3-port separation
    Protection against incorrect measurements or damage
  • Maximum accuracy
  • Specific test report
    Following EN 10204 2.2
  • Protective separation
    according to EN 61140 protects against unpermitted high voltages
  • Maximum reliability
    No repair and failure costs
  • 5-year warranty 

Isolation amplifier for the transmission and conversion of standard 0 to ±20 mA and 0 to ±10 V bipolar signals frequently used in industry, for example, for speed monitoring using tachogenerators.

We look forward to hearing from you!
Contact Us

Technical details

Input: 0 ... (±)10 V, 0 ... (±)20 mA
Output: 0 ... (±)10 V, 0 ... (±)20 mA
Isolation AC/DC: up to 1,000 V
Test Voltage: 4 kV AC
Power Supply: 22 ... 230 V AC/DC
Cutoff Frequency: Cutoff frequency 5 kHz or 10 Hz
Ambient operating temperature: –10 ... 70 °C
Dimensions (W x L x H): 12.5 x 99 x 111 mm
Special features: Convenient configuration via DIP switches, Even after range switching, the transmission ranges remain calibrated and there is no need for re-adjustment, Specifically for precise conversion and galvanic isolation of bipolar signals
Standards: UL 61010-1
Product Category: Isolated Signal Conditioner

Downloads

Manuals

[410] User Manual (DE, EN, FR)
A26000
Version 07

Brochures

[14160] Brochure
Product Overview Interface Technology

Data Sheets

[399] Data sheet
A26000
Product Description | Specifications | Product Range

Certificates

[11745] DNVGL Type Approval Certificate
No. TAA00002H8
Issue No. 2
P150**H1, P150**F1, A260**F1, A260**H1
[11164] EU Declaration of Conformity (DE, EN, FR)
No. EU220125J | 2022-01-25
A260**F1/H1 | P150**F1/H1 | B130**F1
[11437] Certificate of Compliance (UL)
No. 2019-11-22-E340287 (ZT231124D)
Process Control Equipment, Electrical
Series B130** P150** A260** BL513

Software

[12154] Software (.zip)
ePLAN P8 Produktmakros
[11876] Knick Produktmakros (.pdf)
ePLAN Electric P8

Our service

Used in Process or Applications

With the help of hardware in the loop (HIL) tests, prototypes of devices like the traction inverters, for example, can be evaluated in various battery, load, and error situations without having to test the converter itself on test benches or in vehicles.

Related Products

Relevant Blog Posts

Stack and String Voltage Measurement in Electrolyzers and Fuel Cells

Voltage, current and temperature measurement in electrolyzers with P40000 series high voltage transducers

New 30 mV Shunt Resistors for Knick Transducers

Knick is expanding the accessory range for its high-voltage transducers with immediate effect by adding shunt resistors with a 30 mV voltage drop
Innovations at InnoTrans 2024

Innovations at InnoTrans 2024 for rolling stock and DC traction power supply

At InnoTrans 2024 Knick presents electrical measurement solutions for rolling stock and DC traction power supply applications

Knick Austria - direct customer contact in Austria from 2024

Reorganization of sales in Austria and new contacts in the field of process analytics and interface technology

Energy storage - the handshake between renewable energy and electric vehicles

Energy storage technology such as battery and hydrogen are critical for growth and continuous development of renewable energy and e-mobility.

P52000VPD voltage presence detector reliably detects voltages up to 4200 V DC

The new P52000VPD voltage presence detector reliably monitors areas with high voltages and sends a signal to the downstream plant control system when a specified threshold value is reached.

Knick Interface at Battery and Electric & Hybrid Vehicle Technology Expo

Knick will be showcasing high-voltage electrical measurement and signal conversion products.

Quadruple Standard Signals in Just One Signal Conditioner

The A20340 can output a standard input signal to four calibrated and galvanically isolated outputs in parallel.

Electrical measurement and process analytics for hydrogen production

Knick products optimize hydrogen production in the process and in electrolyser operation.

Condition Monitoring of High-Voltage Motors

Having an active predictive maintenance campaign in place for large rotating equipment can be a key strategy for maximizing process uptime.

Pulse frequency conditioner for speed sensors

The new P16000 from Knick is a pulse frequency conditioner that converts frequency signals from speed sensors into standard signals.

Worldwide smallest transducer up to ±2200 V

The P40000 series from Knick enables reliable voltage measurements from ±50 mV to ±3600 V and current measurements from ±100 mA to ±20 kA.

Importance of broad-range power supplies for DC electrical measurement

Many DC electrical measurement products manufactured by Knick contain universal, also known as broad-range, power supplies.

Measuring Photovoltaic Degradation

Photovoltaic (PV) array degradation is an important aspect to consider for system design and installation.

Electrical Measurement Solutions: Control from 480 to 4800 Volts

Voltage and current transducers from Knick bring true control to electrical measurement applications across a wide-range of industries.

Benefits of High Voltage Transducers versus Instrument Transformers

When a need arises to step voltage in a circuit either up or down for purposes of power transmission or distribution, there is no doubt that transformers are essential.

Shunt Resistor versus Hall Effect Technology

There are many systems where measurement of large DC currents are needed for performance and safety.

MTBF beyond 3000 years: A snap hook for your plant

Failure of equipment on the plant floor can lead to considerable and costly disruption.

Knick Products Comply With UL - What Does That Mean?

There are different assessments and approaches to reach an adequate level of safety. Manufacturers are typically on the “safe” side, if they comply with recognized standards.

High-voltage transducer offers more safety on railway vehicles

The requirements placed on railway vehicles have increased significantly in recent years. Products for rolling stock need to ensure a higher level of functional safety than ever before.

True RMS Measurement with P41000TRMS

Traditional millivolt AC transducers are very susceptible to errors due to their poor insulation and are only designed for pure sinewave measurement.

Functional safety and maximum availability can go together

The requirements on operational and safety-related circuits are continuously growing.