A26000 Universal Isolated Signal Conditioner | Input 0…±20 mA or 0…±10 V | Current and voltage measurement
Product number:
A26000
Description
A26000 Universal Isolated Signal Conditioner | Input 0…±20 mA or 0…±10 V | Current and voltage measurement
The specialist for ±10 V and ±20 mA. With calibrated range selection and broad-range power supply.
- Flexible and extremely precise
Calibrated range selection without complicated readjustments - Broad-range power supply
VariPower 20 … 253 V AC/DC - Compact design
12.5 mm modular housing; up to 80 active isolators per meter of mounting rail - Quick and easy configuration
Housing can be easily opened - Pluggable screw terminals
Simple, time-saving assembly and prewiring of enclosures - 3-port separation
Protection against incorrect measurements or damage - Maximum accuracy
- Specific test report
Following EN 10204 2.2 - Protective separation
according to EN 61140 protects against unpermitted high voltages - Maximum reliability
No repair and failure costs - 5-year warranty
Isolation amplifier for the transmission and conversion of standard 0 to ±20 mA and 0 to ±10 V bipolar signals frequently used in industry, for example, for speed monitoring using tachogenerators.
Knick Products Comply With UL - What Does That Mean?
Jan 2018
Interface Technology
There are different assessments and approaches to reach an adequate level of safety. Manufacturers are typically on the “safe” side, if they comply with recognized standards.
We look forward to hearing from you!
Contact Us
Input: | 0 ... (±)10 V, 0 ... (±)20 mA |
---|---|
Output: | 0 ... (±)10 V, 0 ... (±)20 mA |
Isolation AC/DC: | up to 1,000 V |
Test Voltage: | 4 kV AC |
Power Supply: | 22 ... 230 V AC/DC |
Cutoff Frequency: | Cutoff frequency 5 kHz or 10 Hz |
Ambient operating temperature: | –10 ... 70 °C |
Dimensions (W x L x H): | 12.5 x 99 x 111 mm |
Special features: | Convenient configuration via DIP switches, Even after range switching, the transmission ranges remain calibrated and there is no need for re-adjustment, Specifically for precise conversion and galvanic isolation of bipolar signals |
Standards: | UL 61010-1 |
Product Category: | Isolated Signal Conditioner |