P41000 TRMS AC/DC High Voltage Transducer | Input up to ±100 V | True RMS measurement
Description
AC/DC high voltage transducer for True RMS measurement. Input signals from VIN = 60 mV AC up to VIN = 10 V AC
- Universal usability:
- AC Input 60 mV~ to 10 V~
- DC output 0 (4) … 20 mA, 0 … 10 V
- New TransShield technology
allows for extremely compact modular housing - Working voltages up to 3600 V AC/DC
- Protection against electric shock
through protective separation up to 1800 V AC/DC according to EN 61140 - Test voltages up to 15 kV AC
- Excellent transmission properties:
- Gain error Crest factor ≤ 3 < 0.5 %
- Gain error Crest factor 3 … 5 < 1 %
- Response time T90 < 150 ms
- Virtually no influence from common-mode voltages:
CMRR approx. 150 dB - Tremendous flexibility provided by
- Calibrated switching of up to 16 input/output ranges
- Up to 16 customer-specific measuring ranges
- 20 V to 253 V AC/DC broad-range power supply
- Reliable function even with unstable supply
- No damage
in the case of erroneous power connection - Switchable models
minimize required device variants and save stockkeeping costs - Robust
thanks to vacuum encapsulation - Mechanically stable
for operation on ships, rail vehicles and land vehicles - 5-year warranty
The P41000 TRMS isolation amplifiers have been specially conceived for measurements of bipolar voltages ranging from millivolts to volts. They reliably isolate high potentials at the input circuit. Thanks to the true rms conversion in the transducer, even distorted input signals are captured correctly and output as so-called true rms values.
The isolating distances are designed to withstand permanent voltages up to 3600 V AC/DC and fast transients up to 20 kV.
We look forward to hearing from you!
Contact Us
Function: | True-RMS of AC currents via shunt resistor |
---|---|
Input: | 0 ... 10 V AC, 0 ... 50 mV AC |
Output: | 0 ... (±)10 V, 0 ... (±)20 mA, 4 ... 20 mA, peak or TRMS values |
Isolation AC/DC: | up to 3,600 V |
Test Voltage: | 10/15 kV AC |
Power Supply: | 22 ... 230 V AC/DC |
Cutoff Frequency: | Cutoff frequency 5 kHz, lower cutoff frequency on request |
Ambient operating temperature: | –10 ... 70 °C |
Special features: | Exceptionally high MTBF of 2165 years (Mean Time Between Failures), based on field data, Switchable (16 input/output signal combinations) or customized versions |
Product Category: | High Voltage Transducer |