Description
Universal high voltage transducers. Input currents up to Iin = 5 A.
- Universal high voltage transducers
for converting input currents up to 5 A to impressed ±20 mA, ±10 V, or 4 … 20 mA output signals - New TransShield technology
enables extremely compact modular housings - Working voltages
up to 3600 V AC/DC - Protection against electric shock
with protective separation up to 1800 V AC/DC according to EN 61140 - Test voltages up to 15 kV AC
- Excellent transmission properties:
- Gain error < 0.3 %
- Cutoff frequency 5 kHz (low-pass filter / lower cutoff frequency on request)
- Rise time T90 approx. 110 µs
- Tremendous flexibility provided by
- Calibrated switching of up to 16 input/output ranges (working voltage up to 2200 V)
- Up to 16 customer-specific measuring ranges
- 20 V to 253 V AC/DC broad-range power supply
- Reliable function
even with unstable power supply - No damage
in the case of erroneous power connection - Switchable models
minimize required device variants and save stockkeeping costs - Robust
thanks to vacuum encapsulation - Mechanically stable
for operation on ships, rail vehicles and land crafts - 5-year warranty
The P43000 isolation amplifiers have been conceived for direct measurement of currents up to 5 A (DC). They reliably isolate high potentials at the input circuit.
The isolating distances are designed to withstand permanent voltages up to 3600 V AC/DC and fast transients up to 20 kV. Protection against electric shock is achieved through protective separation according to EN 61140 between input and output and power supply.
We look forward to hearing from you!
Contact Us
Function: | Current measurement on high potential |
---|---|
Input: | 0 ... (±)0.1 A upt to 0 ... (±)5 A |
Output: | 0 ... (±)10 V, 0 ... (±)20 mA, 4 ... 20 mA, peak or TRMS values |
Isolation AC/DC: | up to 3,600 V |
Test Voltage: | 10/15 kV AC |
Power Supply: | 22 ... 230 V AC/DC |
Cutoff Frequency: | Cutoff frequency 5 kHz, lower cutoff frequency on request |
Ambient operating temperature: | –10 ... 70 °C, –40 ... 75/85 °C |
Dimensions (W x L x H): | 45 x 90 x 118 mm (D2) |
Special features: | Exceptionally high MTBF of 2165 years (Mean Time Between Failures), based on field data, Switchable or customized versions |
Product Category: | High Voltage Transducer |
Downloads
Data Sheets
Certificates
Our service
Lorem lorem ipsum ipsum dolor sit amet, consetetur sadipscing elitr, sed diam nonumy eirmod tempor invidunt ut labore et dolore magna aliquyam erat, sed diam voluptua. At vero eos et accusam et justo duo dolores et ea rebum. Stet clita kasd gubergren, no sea takimata sanctus est Lorem ipsum dolor sit amet. Lorem ipsum dolor sit amet, consetetur sadipscing elitr, sed diam nonumy eirmod tempor invidunt ut labore et dolore magna aliquyam erat, sed diam voluptua. At vero eos et accusam et justo duo dolores et ea rebum. Stet clita kasd gubergren, no sea takimata sanctus est Lorem ipsum dolor sit amet.